PLUS Series Water to Water Heat Pump
955142SDV
955142SDV
Product Specifications
Recovery L/hr (@20°C ambient and @ 50°C rise)
2448
Heat Exchanger
Copper Tube in Tube Vented
Heating Capacity
142.31 kW
Power Input
28.37 kW
COP
5.02
Recovery @50°C Rise
2448 L/hr
Heat Exchanger Design
Shell in Tube
Maximum DHW Temperature
65 °C
Refrigerant
R134a
TPR Valve Setting (VE/RT/RW)
1000/850/700 kPa
Max Water Pressure Supply without ECV (VE/SS)
800/680/560 kPa
Maximum Water Supply Pressure
660
Electrical Connection Power Supply
3 Phase / 380-415V / 50 Hz
Max Current per Phase (heat pump running, excl pump)
80.6 Amps
Max Current per Phase (2 pumps running only)
7.3 Amps
Min Circuit Size (per phase)
100 Amps
Approx Weight Empty
775 kg
Approx Weight Full
850 kg
Side Clearance
50 mm
Back Clearance
50 mm
Front Clearance
850 mm
Top Clearance
350 mm