Warm Water
Guardian 940240
Guardian 940240
Product Specifications
Installation Location
Indoor/Outdoor
Nominated Maximum Flow Rate
240 L/min
Weight Empty Approx
73 kg
Non-Domestic Warranty: Collectors/Cartridge (Parts/Labour)
2 Years
Ultra Violet Disinfection
Yes
Viewing Window
Audible Lamp Fail Alarm
Volt Free Contacts for Remote Alarm
Hours Run Meter
Max Water Supply Pressure - Static / Dynamic
1000/800 kPa
Thermostatic Control Range
25-60 Degrees C
Max Hot Water Supply Temp (Temporary)
85 Degrees C
Max Outlet Temperature (sanitising)
85 Degrees C
Min Temp Diff Between Cold Supply & Outlet (Flow Conditions)
15 Degrees C
Min Temp Diff Between Hot Supply & Outlet (Flow Conditions)
15 Degrees C
Recommended Minimum recirculation Flow Rate
24 L/min
Recommended Minimum temperature Loss in Recirculation Circuit
2 Degrees C
Technical Documents
Warm Water Spare Parts Guide
275 KB
275 KB
Warm Water Service Manual
3.5 MB
3.5 MB
Guardian with Commpak Drawing
62 KB
62 KB
Guardian with Hiline Pre-Heat Drawing
64 KB
64 KB
Guardian with Loline & Commpak Drawing
76 KB
76 KB
Guardian with Loline Drawing
70 KB
70 KB
Guardian with Raypak Drawing
65 KB
65 KB
Guardian with Storage Drawing
59 KB
59 KB