PLUS Series Air to Water Heat Pump
953202DV
953202DV
Product Specifications
Recovery L/hr (@20°C ambient and @ 50°C rise)
3477
Discharge
Vertical
Heat Exchanger
Copper Tube in Tube Vented
Heating Capacity
211.73 kW
Power Input
49.02 kW
COP
4.32
Recovery @50°C Rise
3642 L/hr
Operating Range (ambient)
0-45 °C
Maximum DHW Temperature
65 °C
Refrigerant
R134a
TPR Valve Setting (VE/RT/RW)
1000/850/700 kPa
Max Water Pressure Supply without ECV (VE/SS)
800/680/560 kPa
Air Flow (at max static pressure)
17778 L/sec
Max Static Pressure
5 Pa
Electrical Connection Power Supply
3 Phase / 380-415V / 50 Hz
Max Current per Phase (heat pump running, excl pump)
169.5 Amps
Max Current per Phase (running pump only)
11 Amps
Min Circuit Size (per phase)
200 Amps
Approx Weight Empty
2200 kg
Approx Weight Full
2300 kg
Evap Coil Side Clearance
1000 mm
Display/Compressor Side Clearance
850 mm
Water Connection Side
850 mm
Top Clearance (vertical discharge)
3500 mm