Tankpak Series 3
Tankpak Series 3 TPE12
Tankpak Series 3 TPE12
Product Specifications
Recovery p/hr (@ 50°C rise)
9875 Litres
Installation Location
Outdoor
Controller
Deluxe
Mounting Options
Back to Back
Thermal Input
2460 MJ/hr
Storage Tanks
2 x A610430
Number of CFWH Units
12
Non-Domestic Warranty: Parts (Parts/Labour)
1 Year
Non-Domestic Warranty: Cylinder/Tank (Labour)
1 Year
Non-Domestic Warranty: Cylinder/Tank (Replacement)
5 Year
Non-Domestic Warranty: Heat Exchanger (Parts/Labour)
1 Year
Tankpak Series 3 Technical Data
Model | Number of CFWH | Thermal Input (MJ/hr) | Recovery @ 50°C Rise (L/hr) | Mounting Options | Standard or Deluxe | 1st Hour Capacity with Nominated Storage Tank |
Electrical Supply 240V 50Hz (STD/DLX) (Amps) |
Electrical Connection STD | Electrical Connection DLX | PHWF & PHWR Pipe Size (mm) | Natural Gas Pipe Size (mm) | Propane Gas Pipe Size (mm) |
Weight Empty*(F/B) STD |
Weight Empty*(F/B) DLX (kg) |
TPI02 TPE02 |
2 | 410 | 1645 | W/F | Standard or Deluxe | 1 x 610340: 1970 1 x 610430: 2055 |
5.1/7.5 | 1.8m 10A plug & lead | 1.8m 10A plug & lead | 25 | 40 | 32 | 251 | 305 |
TPI03 TPE03 |
3 | 615 | 2470 | W/F | Standard or Deluxe | 1 x 610340: 2795 1 x 610430: 2880 |
5.9/8.3 | 1.8m 10A plug & lead | 1.8m 10A plug & lead | 32 | 40 | 32 | 288 | 342 |
TPI04 TPE04 |
4 | 820 | 3290 | W/F/B | Standard or Deluxe | 1 x 610340: 3615 1 x 610430: 3700 |
6.7/9.2 | 1.8m 10A plug & lead | 1.8m 10A plug & lead | 40 | 50 | 32 | 326/306 | 380/360 |
TPI05 TPE05 |
5 | 1025 | 4115 | W/F/B | Standard or Deluxe | 1 x 610430: 4525 | 7.9/10.7 | 1.8m 10A plug & lead | 240V 50Hz single phase hard wired | 40 | 50 | 32 | 390/346 | 444/400 |
TPI06 TPE06 |
6 | 1230 | 4935 | W/F/B | Standard or Deluxe | 1 x 610430: 5345 | 8.8/11.5 | 1.8m 10A plug & lead | 240V 50Hz single phase hard wired | 40 | 50 | 32 | 427/370 | 481/424 |
TPI07 TPE07 |
7 | 1435 | 5760 | W/F/B | Deluxe | 1 x 610430: 6170 | 12.4 | - | 240V 50Hz single phase hard wired | 50 | 50 | 32 | - | 527/476 |
TPI08 TPE08 |
8 | 1640 | 6580 | W/F/B | Deluxe | 2 x 610430: 7400 | 14.5 | - | 240V 50Hz single phase hard wired | 50 | 65 | 40 | - | 702/633 |
TPI09 TPE09 |
9 | 1845 | 7405 | W/F/B | Deluxe | 2 x 610430: 8225 | 15.3 | - | 240V 50Hz single phase hard wired | 50 | 65 | 40 | - | 766/701 |
TPI10 TPE10 |
10 | 2050 | 8225 | B | Deluxe | 2 x 610430: 9045 | 16.1 | - | 240V 50Hz single phase hard wired | 50 | 65 | 40 | - | 725 |
TPI12 TPE12 |
12 | 2460 | 9875 | B | Deluxe | 2 x 610430: 10695 | 17.8 | - | 240V 50Hz single phase hard wired | 50 | 80 | 40 | - | 907 |
TPI14 TPE14 |
14 | 2870 | 11520 | B | Deluxe | 3 x 610430: 12750 | 19.5 | - | 240V 50Hz single phase hard wired | 65 | 80 | 50 | - | 981 |
TPI16 TPE16 |
16 | 3280 | 13165 | B | Deluxe | 3 x 610430: 14395 | 21.1 | - | 240V 50Hz single phase hard wired | 65 | 80 | 50 | - | 1047 |
TPI18 TPE18 |
18 | 3690 | 14810 | B | Deluxe | 3 x 610430: 16040 | 22.7 | - | 240V 50Hz single phase hard wired | 65 | 80 | 50 | - | 1143 |
Weight includes CFWH unit, 610430 storage tank/s, 1 x primary pump, frame and preassembled manifolds. Note: Add 48.2kg for CM3-2 & CM5-2 D/S Primary assy, 63.8kg for CM10-1 D/S primary assy, 19.4 kg for UPM3 D/S secondary assy and 22.7 kg for UPMXL D/S secondary assy.
Technical Documents
TankPak Series 3 Service Manual - Deluxe
3.7 MB
3.7 MB
TankPak Series 3 Service Manual - Standard
2.1 MB
2.1 MB