Raypak Hot Water
Raypak 200
Raypak 200
Product Specifications
Max Storage Capacity
2000 Litres
Installation Location
Indoor/Outdoor
Weight Empty Approx
91 kg
Natural Gas Input
196 MJ/hr
Natural Gas Output
44 kW
Inlet Connection
RC1½
ULPG Input
185 MJ/hr
ULPG Output
41 kW
Warranty: Parts (Parts/Labour)
1 Year
Warranty: Heat Exchanger (Parts/Labour)
5/1 Year
Dimensions H x W (includes high wind top)
1955 x 465 mm
Dimensions H x W (without high wind top)
1625 x 465 mm
Flue Connection
175 mm
Natural Gas Connection Modulating Models
RP1
ULPG Connection - Modulating Models
RP¾
Relief Valve Connections - Modulating Models
RC¾
Electrical Rating 240V 50Hz
50 Watts
Electrical Rating 240v 50Hz
50 Amps
Minimum Buffer Tank Capacity
325 Litres
Natural Gas Recovery per/hr @ 30°C rise
1250 Litres
Natural Gas Recovery per/hr @ 40°C rise
937 Litres
Natural Gas Recovery per/hr @ 50°C rise
750 Litres
Natural Gas Recovery per/hr @ 60°C rise
625 Litres
Natural Gas Recovery per/hr @ 65°C rise
577 Litres
Natural Gas Recovery per/hr @ 70°C rise
536 Litres
Natural Gas Recovery per/hr @ 75°C rise
500 Litres
Natural Gas Recovery per/hr @ 80°C rise
469 Litres
Natural Gas Recovery per/hr @ 85C rise
441 Litres
Maximum Flow Rate Modulating (10°C Rise)
1.04 Litres/sec
Maximum Flow Rate Modulating Pressure Drop
3 kPa
Maximum Flow Rate On/Off (15°C Rise)
0.69 Litres/sec
Maximum Flow Rate On/Off Pressure Drop
3 kPa
Minimum Flow Rate (20°C Rise)
0.52 Litres/sec
Minimum Flow Rate Pressure Drop
3 kPa
Back Clearance (Combustibles)
500 mm
Front Clearance (Combustibles)
750 mm
Left Clearance (Combustibles)
600 mm
Right Clearance (Combustibles)
500 mm
Ceiling Clearance (Combustibles)
1200 mm
Back Clearance (Non-Combustibles)
150 mm
Front Clearance (Non-Combustibles)
750 mm
Left Clearance (Non-Combustibles)
600 mm
Right Clearance (Non-Combustibles)
150 mm
Ceiling Clearance (Non-Combustibles)
1200 mm
Thermostat Settings
Modulating | Maximum Setting | 95°C |
Factory Setting | 78°C | |
Minimum Setting | 44°C | |
On/Off | Maximum Setting | 80°C |
Factory Setting | 50°C | |
Minimum Setting | 44°C |
Gas Pressure
Model |
|
200-430 |
538-4224 |
Natural Gas | Minimum Pressure | 1.13 kPa | 1.13 kPa |
Test Point | 0.77 kPa | ||
Maximum Pressure | 3.50 kPa | ||
ULPG | Minimum Pressure | 2.75 kPa | - |
Test Point | 2.75 kPa | - | |
Maximum Pressure | 3.50 kPa | - |
Technical Documents

Raypak 200-430 Water Heater Service Instructions
2.3 MB
2.3 MB